Summary
JDCF voltage transformer is a kind of outdoor fully-enclosed magnetic oil-paper insulated voltage & electricity measuring and relay protection device used in neutral point earthing power system with maximum voltage of 126kV and rated frequency of 50Hz or 60Hz.
JDCF has reliable design and low magnetic flux, able to avoid resonance overvoltage. Secondary windings separate measuring and protection. The measuring precision can reach Level 0.2, meeting different user requirements and high precision measuring requirements put forward by power departments.
JDCF has metal expander with stainless steel shell and the sealing adopts imported cushion. The body adopts advanced vacuum drying and vacuum oil treatment technique, featuring small dielectric loss and low partial discharging volume and enabling e the product run reliably and safely.
Working Environment
Ambient Temperature: Max. Atmospheric Temperature: +40℃; Min. Atmospheric Temperature: -30℃; Daily average atmospheric temperature: ≤+30℃
Altitude: JDCF-110, JDCF-110W1, JDCF-110W2 Voltage Transformer: ≤ 1,000m, JDCF-110GY Voltage Transformer: ≤ 3,000m
Main Technical Parameters
No | Name | Unit | Data |
1 | Rated Voltage | kV | 110 |
2 | Rated Frequency | Hz | 50 |
3 | Phase Number | Single-phase | |
4 | Rated Voltage of Primary Winding | V | 11000/√3 |
5 | Rated Voltage of Secondary Winding | V | 100/√3 |
6 | Rated Voltage of Reminding Windings | V | 100 |
7 | Load Limit of Secondary Winding | VA | 2000 |
8 | Load Limit of Secondary Winding | 3P、300VA | |
9 | Accuracy | 0.2/0.5/3P 0.2(or0.5)/3P/3P | |
10 | Rated Output | VA | 100VA/250VA/300VA 100VA/500VA/300VA |
11 | Total Weight | kg | 730 |
Notice for Ordering
When ordering, please specify: product name, model, current ratio, level composition, quantity, etc.
Please specify clearly if the product is used in polluted areas or places with altitude above 1,000m or other special requirements shall be met.
Overall Dimension Drawing