Summary
LABN6-35 current transformer (LABN6-35) is a kind of outdoor fully-enclosed capacitance oil-paper insulated current & electricity measuring and relay protection device used in alternative current (AC) power system with maximum voltage of 140.5kV and rated frequency of 50Hz or 60Hz.
LABN6-35, with 3 or 4 pieces of secondary windings, adopts secondary measuring windings made of highly magnetism-conductive microcrystalline alloy, able to guarantee the measuring precise to Level 0.2 or 0.2S.
The oil conservator adopts aluminum alloy and the oil tank is drawn and formed by a whole piece of excellent steel plate. Sealed structure can extend the aging period of gasket rings and keep reliable sealing performance. Enclosed structure can guarantee the running quality of insulated oil and keep safe and reliable running.
Working Environment
Ambient Temperature: Max. Atmospheric Temperature: +40℃; Min. Atmospheric Temperature: -30℃; Daily average atmospheric temperature: ≤+30℃
Altitude no more than 1,000m (able to provide special products)
Main Technical Parameters
No | Name | Unit | Data |
1 | Rated Voltage | kV | 35 |
2 | Rated Primary Current | A | 5、10、15、20、30、40、 50、75、100、150、200、 300、400、500、600、750、 800、1000、1200、1500、2000 |
3 | Rated Secondary Current | A | 5 |
4 | Accurate Level Composition | 0.2(0.2s)Level 30VA 0.5Level 40VA 10P1Level 40VA 10P2Level 30VA | |
5 | Instrument Security Coefficient | ≤10 | |
6 | Accurate Limit Coefficient | ≥20 | |
7 | Total Weight | kg | 190 |
Notice for Ordering
When placing the order, please specify the following items clearly
Product Mode, Rated Current Ratio, Accurate Level Composition
Overall Dimension Drawing
Previous:JDCF-110 Voltage Transformer