GW4-40.5 Outdoor High Voltage Disconnecting Switch
SummaryGW4-40.5 outdoor AC high voltage disconnecting switch is applied as connecting & disconnecting voltage without load in three phase AC 50-60Hz power system with maximum voltage of 40.5kV.The earthing switches are divided into non-earthing, single earthing and double earthing according to s ...
Details

Summary

GW4-40.5 outdoor AC high voltage disconnecting switch is applied as connecting & disconnecting voltage without load in three phase AC 50-60Hz power system with maximum voltage of 40.5kV.

The earthing switches are divided into non-earthing, single earthing and double earthing according to structure and common type and anti-pollution type (w) according to application areas. Besides, they have type I and type II structures and the electrical parameters of the latter have the same short circuit performance bearing capacity as the main pole.

The product is equipped with manual operation mechanism and electromagnetic lock which prevents false operation.

All the external components adopts aluminum alloy, stainless steel or hot galvanizing techniques, enabling no corrosion under long-term operation and five kinds of protection performances.

 

Working Environment

Altitude no more than ≤ 1,000m (able to provide special products)

Ambient Temperature: -30℃ -+40℃ (alpine region: -40℃)

Wind velocity no more than 35m/s

Earthquake level no more than level 8

Ice thickness no more than 10mm

Installation areas are free of serious dust, dirt, combustible materials, explosion danger, chemical corrosion or violent vibration

Installation base shall be horizontal

 

Main Technical Parameters

ModelGW-
40.5/
630
GW-
40.5/
1000
GW-
40.5/
1250
GW-
40.5D/
630
GW-
40.5D/
1000
GW-
40.5D/
1250
GW-
40.5DII/
630
GW-
40.5DII/
1250
GW-
40.5D/
2000
GW-
40.5DII/
2000

Rated Voltage KV

40.540.540.540.540.540.540.540.540.540.5

Rated Current A

6301000125063010001250630125020002000

Dynamic Stable Current (peak value) KA

5080805080805080100100

Rated Thermal Stability Current

2031.531.52031.531.52031.54040

Rated Thermal Stability Time

4444444433

Power Frequency Withstanding Voltage per Minute KV

90909090909090909090

Lightning Impact Withstanding Voltage KV

210210210210210210210210210210

Single Pole Weight

187191191187219219223291275345

Equipped Mechanism

Disconnecting Switches

CS11

CS11CS11CS8-6DCS8-6DCS8-6DCS14GCS14GCS14GCS14G

Earthing Switches




CS8-6DCS8-6DCS8-6DCS14GCS14GCS14GCS14G

 

Notice for Ordering

When placing the order, please specify: product model, name, rated current, rated voltage, equipped with earthing switches or not, etc.

When ordering the disconnecting switches of the earthing switches, please specify single or double earthing, type I or type II;

Please specify whether operation mechanism, model, name are required;

Please specify which kind of power supply and voltage level is adopted for the electromagnetic lock in the operation mechanism;

If it is high profile layout, please specify the layout number.

 

Overall Dimension Drawing


gHj7h3SSQyWN0og8U-0WIw

Previous:没有了

Next:没有了

Related Products

WhatsApp

+86-87315588

E-mail

532381564@qq.com

Tel

+86-18817261186

TOP

no cache
Processed in 0.626755 Second.